Specifications for DTK400
Mounting Pipe
Power Supply 24 V AC +/- 15% or 18…33 V DC, 0,1 VA
Dimensions, external (WxHxD) 40x79x mm
Analogue output load impedance 0...10v > 10kOhm
Measuring range 0-400 kPa
Max. overload pressure 1200 kPa
Max. system pressure 25 bar
Accuracy, resolution sensor ±0.8 % fs
Cabel Three wire cable, 1.5 m
Specifications for Differential pressure transmitter for liquids and gases
Protection class IP65
Storage temperature -15…85 °C
Media liquids and gases
Pressure connection 6 mm for copper tube
Dynamic response time <5 ms
Material, housing Stainless steel
Material sensor Ceramic material

Accessories