HCA281DW-3 Exigo Ardo - Configurable 24 V heating controller
This article is discontinued
Exigo Ardo are controllers for heating and boiler control that make every step from installation to operation and maintenance easier than ever. Simply connect the controller, enter any settings as desired and start up. It can be used either stand-alone or integrated into a network. It has built-in support for many different languages and is designed for mounting on a DIN-rail or in a cabinet door.
The Exigo* controllers are BTL listed, click here to go to the BACnet International website where you'll find PICS documents and more information.
Click here to visit our application selector site where you can find pre-programmed application examples. If you like, you can use them as they are or modify them for your needs using Application tool. There are pictures showing each example to help you find the right one.
Navigate on this page
Specifications
Inputs/Outputs | 28 |
---|---|
Communication ports | 1 |
Supply voltage | 24 V AC ± 15 %, 50...60 Hz or 21...36 V DC |
---|---|
Ambient temperature | 0…50°C |
Storage temperature | -20…+70°C |
Ambient humidity | Max. 95 % RH |
Protection class | IP20 |
Connection | Disconnectable terminal strips, 4 mm 2 |
Memory backup | Built-in long life battery gives long backup time of all settings incl. real time |
Display | Backlit LCD, 4 rows of 20 characters |
Mounting | DIN-rail or cabinet |
Casing | Standard Euronorm (8.5 modules wide) |
Dimensions (WxHxD) | 149 x 121 x 60mm |
Ethernet | EXOline, Modbus, BACnet/IP, CLOUDigo |
RS485 | EXOline, Modbus, BACnet MS/TP |
M-Bus | M-Bus communication |
Analogue inputs (AI) | For PT1000 sensors (accuracy ± 0.4°C), Ni1000 sensors or 0...10 V DC (accuracy ± 0.15 % of full output signal). 12 bit resolution in the A/D conversion. |
Digital inputs (DI) | For potential-free contacts |
Universal inputs (UI) | AI or DI |
Analogue outputs (AO) | 0...10 V DC, 1 mA, short-circuit protected |
Digital outputs (DO) | Mosfet outputs, 24 V AC or DC, 2 A continuous. Max. 8 A in total. |
Software & documentation
Product sheet
Instructions
Manuals
Accessories
External touch screen display
External display
Front mounting kit, room for one controller
Ardo expansion unit with15 I/O:s
3 m cable for connecting an external display
10 m cable for connecting an external display
Cable for USB connection
Ardo expansion unit with 28 I/O:s
Vido expansion unit with 19 I/O:s
Set of plug-in terminals for models with 15 I/O:s