Regin
RC-C3H-BLACK Regio Midi – Pre-programmed room controllers with communication
Regio Midi are controllers with a built-in temperature sensor and an RS485 communication port. Controllers in different rooms and zones can be connected to a bus line enabling communication with a central SCADA system via RS485 (EXOline, BACnet (only display versions) or Modbus).
Navigate on this page
Specifications
Controller Type | Room Control |
---|---|
Power Supply | 24V AC |
Mounting | Wall mount |
Display | No |
Supported protocols | EXOline, Modbus, BACnet |
Port type | RS-485 |
Power Supply | 24VAC (18...30 V AC 50/60Hz / ), 2.5 VA |
Dimensions, external (WxHxD) | 95x95x38 mm |
Supported protocols | EXOline, Modbus |
AI | 1 |
UI | 1 |
DI | 1 |
DI/CI | 1 |
UO | 3 |
DO | 0 |
Occupancy button | No |
3-step fan control | No |
EC Fan Control | Yes |
Setpoint knob | No |
Hidden setpoint | Yes |
CO2 Sensor | No |
Display | No |
Protection class | IP20 |
---|---|
Ambient humidity (non-condensing) | 0…90 % RH |
Storage temperature | -20…70 °C |
Mounting | Room |
Weight, incl. packaging | 0.11 kg |
Analogue inputs type (AI) | PT1000, 0...50°C, 0...10 V |
Universal inputs type (UI) | PT1000 / DI |
Condensation inputs type (CI) | Digital input for condensation detector KG-A/1 |
Universal outputs type (UO) | DO 24 V AC/1A, AO 0...10 V/5mA |
Accuracy, temperature 1 | ±0.5 °K @ 15...30 °C |
Material, housing | Polycarbonate, PC |
Software & documentation
Product sheet
Instructions
Accessories
RB3
Relay unit for RC-...F... controllers
X1178
Power interface for RC-...F... controllers
KG-A/1
Condensation detector for Regio controllers, 1 m cable length
RC-CONN:10
A set of 10 connector plates for RC units
RCC-CONN:10
A set of 10 connector plates for RCC units
RC-TEST
Service adapter for all Regio room units