Regin

Differential pressure transmitter for liquids and gases

Differential pressure transmitter for measurement of liquids (also glycol-mixed) and gases (not ammonia). The measuring element is made of ceramic material.

Articles

(18 st)
  • DTK10 - Regin
    DTK10
    Differential pressure transmitter
    Mounting
    Pipe
    Power Supply
    24 V AC +/- 15% or 18…33 V DC, 0,1 VA
    Dimensions, external (WxHxD)
    40x79x mm
    Analogue output load impedance 0...10v
    > 10kOhm
    Measuring range
    0-10 kPa
    Max. overload pressure
    60 kPa
    Max. system pressure
    25 bar
    Accuracy, resolution sensor
    ±1.3 % fs
    Cabel
    Three wire cable, 1.5 m
  • DTK10-420 - Regin
    DTK10-420
    Differential pressure transmitter
    Mounting
    Pipe
    Power Supply
    11…33 V DC, 0.5 VA
    Dimensions, external (WxHxD)
    40x79x mm
    Analogue output load impedance 4...20mA
    <650 Ohm (at 24 V DC)
    Measuring range
    0-10 kPa
    Max. overload pressure
    60 kPa
    Max. system pressure
    25 bar
    Accuracy, resolution sensor
    ±1.3 % fs
    Cabel
    Two wire cable, 1.5 m
  • DTK20 - Regin
    DTK20
    Differential pressure transmitter
    Mounting
    Pipe
    Power Supply
    24 V AC +/- 15% or 18…33 V DC, 0,1 VA
    Dimensions, external (WxHxD)
    40x79x mm
    Analogue output load impedance 0...10v
    > 10kOhm
    Measuring range
    0-20 kPa
    Max. overload pressure
    120 kPa
    Max. system pressure
    25 bar
    Accuracy, resolution sensor
    ±1.3 % fs
    Cabel
    Three wire cable, 1.5 m
  • DTK20-420 - Regin
    DTK20-420
    Differential pressure transmitter
    Mounting
    Pipe
    Power Supply
    11…33 V DC, 0.5 VA
    Dimensions, external (WxHxD)
    40x79x mm
    Analogue output load impedance 4...20mA
    <650 Ohm (at 24 V DC)
    Measuring range
    0-20 kPa
    Max. overload pressure
    120 kPa
    Max. system pressure
    25 bar
    Accuracy, resolution sensor
    ±1.3 % fs
    Cabel
    Two wire cable, 1.5 m
  • DTK40 - Regin
    DTK40
    Differential pressure transmitter
    Mounting
    Pipe
    Power Supply
    24 V AC +/- 15% or 18…33 V DC, 0,1 VA
    Dimensions, external (WxHxD)
    40x79x mm
    Analogue output load impedance 0...10v
    > 10kOhm
    Measuring range
    0-40 kPa
    Max. overload pressure
    200 kPa
    Max. system pressure
    25 bar
    Accuracy, resolution sensor
    ±1.3 % fs
    Cabel
    Three wire cable, 1.5 m
  • DTK40-420 - Regin
    DTK40-420
    Differential pressure transmitter
    Mounting
    Pipe
    Power Supply
    11…33 V DC, 0.5 VA
    Dimensions, external (WxHxD)
    40x79x mm
    Analogue output load impedance 4...20mA
    <650 Ohm (at 24 V DC)
    Measuring range
    0-40 kPa
    Max. overload pressure
    200 kPa
    Max. system pressure
    25 bar
    Accuracy, resolution sensor
    ±1.3 % fs
    Cabel
    Two wire cable, 1.5 m
  • DTK100 - Regin
    DTK100
    Differential pressure transmitter
    Mounting
    Pipe
    Power Supply
    24 V AC +/- 15% or 18…33 V DC, 0,1 VA
    Dimensions, external (WxHxD)
    40x79x mm
    Analogue output load impedance 0...10v
    > 10kOhm
    Measuring range
    0-100 kPa
    Max. overload pressure
    500 kPa
    Max. system pressure
    25 bar
    Accuracy, resolution sensor
    ±1.3 % fs
    Cabel
    Three wire cable, 1.5 m
  • DTK100-420 - Regin
    DTK100-420
    Differential pressure transmitter
    Mounting
    Pipe
    Power Supply
    11…33 V DC, 0.5 VA
    Dimensions, external (WxHxD)
    40x79x mm
    Analogue output load impedance 4...20mA
    <650 Ohm (at 24 V DC)
    Measuring range
    0-100 kPa
    Max. overload pressure
    500 kPa
    Max. system pressure
    25 bar
    Accuracy, resolution sensor
    ±1.3 % fs
    Cabel
    Two wire cable, 1.5 m
  • DTK250 - Regin
    DTK250
    Differential pressure transmitter
    Mounting
    Pipe
    Power Supply
    24 V AC +/- 15% or 18…33 V DC, 0,1 VA
    Dimensions, external (WxHxD)
    40x79x mm
    Analogue output load impedance 0...10v
    > 10kOhm
    Measuring range
    0-250 kPa
    Max. overload pressure
    1200 kPa
    Max. system pressure
    25 bar
    Accuracy, resolution sensor
    ±1.3 % fs
    Cabel
    Three wire cable, 1.5 m
  • DTK250-420 - Regin
    DTK250-420
    Differential pressure transmitter
    Mounting
    Pipe
    Power Supply
    11…33 V DC, 0.5 VA
    Dimensions, external (WxHxD)
    40x79x mm
    Analogue output load impedance 4...20mA
    <650 Ohm (at 24 V DC)
    Measuring range
    0-250 kPa
    Max. overload pressure
    1200 kPa
    Max. system pressure
    25 bar
    Accuracy, resolution sensor
    ±1.3 % fs
    Cabel
    Two wire cable, 1.5 m
  • DTK400 - Regin
    DTK400
    Differential pressure transmitter
    Mounting
    Pipe
    Power Supply
    24 V AC +/- 15% or 18…33 V DC, 0,1 VA
    Dimensions, external (WxHxD)
    40x79x mm
    Analogue output load impedance 0...10v
    > 10kOhm
    Measuring range
    0-400 kPa
    Max. overload pressure
    1200 kPa
    Max. system pressure
    25 bar
    Accuracy, resolution sensor
    ±0.8 % fs
    Cabel
    Three wire cable, 1.5 m
  • DTK400-420 - Regin
    DTK400-420
    Differential pressure transmitter
    Mounting
    Pipe
    Power Supply
    11…33 V DC, 0.5 VA
    Dimensions, external (WxHxD)
    40x79x mm
    Analogue output load impedance 4...20mA
    <650 Ohm (at 24 V DC)
    Measuring range
    0-400 kPa
    Max. overload pressure
    1200 kPa
    Max. system pressure
    25 bar
    Accuracy, resolution sensor
    ±0.8 % fs
    Cabel
    Two wire cable, 1.5 m
  • DTK600 - Regin
    DTK600
    Differential pressure transmitter
    Mounting
    Pipe
    Power Supply
    24 V AC +/- 15% or 18…33 V DC, 0,1 VA
    Dimensions, external (WxHxD)
    40x79x mm
    Analogue output load impedance 0...10v
    > 10kOhm
    Measuring range
    0-600 kPa
    Max. overload pressure
    1200 kPa
    Max. system pressure
    25 bar
    Accuracy, resolution sensor
    ±0.5 % fs
    Cabel
    Three wire cable, 1.5 m
  • DTK600-420 - Regin
    DTK600-420
    Differential pressure transmitter
    Mounting
    Pipe
    Power Supply
    11…33 V DC, 0.5 VA
    Dimensions, external (WxHxD)
    40x79x mm
    Analogue output load impedance 4...20mA
    <650 Ohm (at 24 V DC)
    Measuring range
    0-600 kPa
    Max. overload pressure
    1200 kPa
    Max. system pressure
    25 bar
    Accuracy, resolution sensor
    ±0.5 % fs
    Cabel
    Two wire cable, 1.5 m
  • DTK1000 - Regin
    DTK1000
    Differential pressure transmitter
    Mounting
    Pipe
    Power Supply
    24 V AC +/- 15% or 18…33 V DC, 0,1 VA
    Dimensions, external (WxHxD)
    40x79x mm
    Analogue output load impedance 0...10v
    > 10kOhm
    Measuring range
    0-1000 kPa
    Max. overload pressure
    2000 kPa
    Max. system pressure
    50 bar
    Accuracy, resolution sensor
    ±0.5 % fs
    Cabel
    Three wire cable, 1.5 m
  • DTK1000-420 - Regin
    DTK1000-420
    Differential pressure transmitter
    Mounting
    Pipe
    Power Supply
    11…33 V DC, 0.5 VA
    Dimensions, external (WxHxD)
    40x79x mm
    Analogue output load impedance 4...20mA
    <650 Ohm (at 24 V DC)
    Measuring range
    0-1000 kPa
    Max. overload pressure
    2000 kPa
    Max. system pressure
    50 bar
    Accuracy, resolution sensor
    ±0.5 % fs
    Cabel
    Two wire cable, 1.5 m
  • DTK1600 - Regin
    DTK1600
    Differential pressure transmitter
    Mounting
    Pipe
    Power Supply
    24 V AC +/- 15% or 18…33 V DC, 0,1 VA
    Dimensions, external (WxHxD)
    40x79x mm
    Analogue output load impedance 0...10v
    > 10kOhm
    Measuring range
    0-1600 kPa
    Max. overload pressure
    3200 kPa
    Max. system pressure
    50 bar
    Accuracy, resolution sensor
    ±0.5 % fs
    Cabel
    Three wire cable, 1.5 m
  • DTK1600-420 - Regin
    DTK1600-420
    Differential pressure transmitter
    Mounting
    Pipe
    Power Supply
    11…33 V DC, 0.5 VA
    Dimensions, external (WxHxD)
    40x79x mm
    Analogue output load impedance 4...20mA
    <650 Ohm (at 24 V DC)
    Measuring range
    0-1600 kPa
    Max. overload pressure
    3200 kPa
    Max. system pressure
    50 bar
    Accuracy, resolution sensor
    ±0.5 % fs
    Cabel
    Two wire cable, 1.5 m

Specifications

Specifications for Differential pressure transmitter for liquids and gases
Protection class IP65
Storage temperature -15…85 °C
Media liquids and gases
Pressure connection 6 mm for copper tube
Dynamic response time <5 ms
Material, housing Stainless steel
Material sensor Ceramic material

Accessories