(4 st)-
TLT100
- Power Supply
- 24VAC/DC (18...24 V AC 50Hz / 18...35 V DC), VA
- Dimensions, external (WxHxD)
- 75x177x75 mm
- Insertion length
- …120
- Diameter, well
- 8 mm
- Analogue output load impedance 0...10v
- Min. 10 kΩ
- Measuring range, temp
- 0…100 °C
- Output temperature
- 0-10 V
- Material well
- Nickel plated brass/copper
-
TLT100-420
- Power Supply
- 24VAC/DC (... V AC 50Hz / 11...30 V DC), VA
- Dimensions, external (WxHxD)
- 75x177x75 mm
- Insertion length
- …120
- Diameter, well
- 8 mm
- Analogue output load impedance 4...20mA
- max. 500 Ω
- Measuring range, temp
- 0…100 °C
- Output temperature
- 4-20 mA
- Material well
- Nickel plated brass/copper
-
TLT50
- Power Supply
- 24VAC/DC (18...24 V AC 50Hz / 18...35 V DC), VA
- Dimensions, external (WxHxD)
- 75x177x75 mm
- Insertion length
- …120
- Diameter, well
- 8 mm
- Analogue output load impedance 0...10v
- Min. 10 kΩ
- Measuring range, temp
- -30…50 °C
- Output temperature
- 0-10 V
- Material well
- Nickel plated brass/copper
-
TLT50-420
- Power Supply
- 24VAC/DC (... V AC 50Hz / 11...30 V DC), VA
- Dimensions, external (WxHxD)
- 75x177x75 mm
- Insertion length
- …120
- Diameter, well
- 8 mm
- Analogue output load impedance 4...20mA
- max. 500 Ω
- Measuring range, temp
- -30…50 °C
- Output temperature
- 4-20 mA
- Material well
- Nickel plated brass/copper
Specifications
Protection class | IP65 |
---|---|
Storage temperature | -20…70 °C |
Weight, incl. packaging | 0.25 kg |
(Well/Pressure) connection | R 1/2 " |
Accuracy, temperature 1 | ±2 °K @ 0...100 °C |
Cable gland | M16x1,5 |
Terminal wire size | 1.5 mm² |
Material, housing | Polycarbonate (PC) |
Material sensor | Nickel plated brass |
Software & documentation
Product sheet
Instructions
Accessories
DR-31/14
Stainless steel pocket AISI 304, 120 mm, ø external 9 mm, ø internal 7 mm, connection R 1/2"