Navigate on this page
Articles
(7 st)-
PDTX12-C
- Power Supply
- 24VAC/DC (21...27 V AC 50Hz / 21...27 V DC), 4.0 VA
- Dimensions, external (WxHxD)
- 167x46x130 mm
- Max Overvoltage on any terminal
- Max. ±18 V (referenced to GND) V
- Analogue output load impedance 0...10v
- Min. 10 kΩ
- Pressure, range sensor
- 0…1250 Pa
- Accuracy, pressure sensor 1
- ≤ 1 % full scale %
- Max. allowed diff. Pressure sensor 1
- 25 kPa
- Damping (electronic)
- settable 1…12 s
- Unit. Range l/s
- 0…31000
- Unit. Range m3/h
- 0…65000 (factory setting)
- Unit. Range CFM [Ft3/min]
- 0…65000
-
PDTX25-C
- Power Supply
- 24VAC/DC (21...27 V AC 50Hz / 21...27 V DC), 4.0 VA
- Dimensions, external (WxHxD)
- 167x46x130 mm
- Max Overvoltage on any terminal
- Max. ±18 V (referenced to GND) V
- Analogue output load impedance 0...10v
- Min. 10 kΩ
- Pressure, range sensor
- 0…2500 Pa
- Accuracy, pressure sensor 1
- ≤ 1 % full scale %
- Max. allowed diff. Pressure sensor 1
- 50 kPa
- Damping (electronic)
- settable 1…12 s
- Unit. Range l/s
- 0…31000
- Unit. Range m3/h
- 0…65000 (factory setting)
- Unit. Range CFM [Ft3/min]
- 0…65000
-
PDTX75-C
- Power Supply
- 24VAC/DC (21...27 V AC 50Hz / 21...27 V DC), 4.0 VA
- Dimensions, external (WxHxD)
- 167x46x130 mm
- Max Overvoltage on any terminal
- Max. ±18 V (referenced to GND) V
- Analogue output load impedance 0...10v
- Min. 10 kΩ
- Pressure, range sensor
- 0…7500 Pa
- Accuracy, pressure sensor 1
- ≤ 1 % full scale %
- Max. allowed diff. Pressure sensor 1
- 120 kPa
- Damping (electronic)
- settable 1…12 s
- Unit. Range l/s
- 0…31000
- Unit. Range m3/h
- 0…65000 (factory setting)
- Unit. Range CFM [Ft3/min]
- 0…65000
-
PDTX12-2-C
- Power Supply
- 24VAC/DC (21...27 V AC 50Hz / 21...27 V DC), 4.0 VA
- Dimensions, external (WxHxD)
- 167x46x130 mm
- Max Overvoltage on any terminal
- Max. ±18 V (referenced to GND) V
- Analogue output load impedance 0...10v
- Min. 10 kΩ
- Pressure, range sensor
- 0…1250 Pa
- Pressure, range sensor 2
- 0…1250 Pa
- Accuracy, pressure sensor 1
- ≤ 1 % full scale %
- Accuracy, pressure sensor 2
- ≤ 1 % full scale %
- Max. allowed diff. Pressure sensor 1
- 25 kPa
- Max. allowed diff. Pressure sensor 2
- 25 kPa
- Damping (electronic)
- settable 1…12 s
- Unit. Range l/s
- 0…31000
- Unit. Range m3/h
- 0…65000 (factory setting)
-
PDTX25-2-C
- Power Supply
- 24VAC/DC (21...27 V AC 50Hz / 21...27 V DC), 4.0 VA
- Dimensions, external (WxHxD)
- 167x46x130 mm
- Max Overvoltage on any terminal
- Max. ±18 V (referenced to GND) V
- Analogue output load impedance 0...10v
- Min. 10 kΩ
- Pressure, range sensor
- 0…2500 Pa
- Pressure, range sensor 2
- 0…2500 Pa
- Accuracy, pressure sensor 1
- ≤ 1 % full scale %
- Accuracy, pressure sensor 2
- ≤ 1 % full scale %
- Max. allowed diff. Pressure sensor 1
- 50 kPa
- Max. allowed diff. Pressure sensor 2
- 50 kPa
- Damping (electronic)
- settable 1…12 s
- Unit. Range l/s
- 0…31000
- Unit. Range m3/h
- 0…65000 (factory setting)
-
PDTX12S25-C
- Power Supply
- 24VAC/DC (21...27 V AC 50Hz / 21...27 V DC), 4.0 VA
- Dimensions, external (WxHxD)
- 167x46x130 mm
- Max Overvoltage on any terminal
- Max. ±18 V (referenced to GND) V
- Analogue output load impedance 0...10v
- Min. 10 kΩ
- Pressure, range sensor
- 0…1250 Pa
- Pressure, range sensor 2
- 0…2500 Pa
- Accuracy, pressure sensor 1
- ≤ 1 % full scale %
- Accuracy, pressure sensor 2
- ≤ 1 % full scale %
- Max. allowed diff. Pressure sensor 1
- 25 kPa
- Max. allowed diff. Pressure sensor 2
- 50 kPa
- Damping (electronic)
- settable 1…12 s
- Unit. Range l/s
- 0…31000
- Unit. Range m3/h
- 0…65000 (factory setting)
-
PDTX12S75-C
- Power Supply
- 24VAC/DC (21...27 V AC 50Hz / 21...27 V DC), 4.0 VA
- Dimensions, external (WxHxD)
- 167x46x130 mm
- Max Overvoltage on any terminal
- Max. ±18 V (referenced to GND) V
- Analogue output load impedance 0...10v
- Min. 10 kΩ
- Pressure, range sensor
- 0…1250 Pa
- Pressure, range sensor 2
- 0…7500 Pa
- Accuracy, pressure sensor 1
- ≤ 1 % full scale %
- Accuracy, pressure sensor 2
- ≤ 1 % full scale %
- Max. allowed diff. Pressure sensor 1
- 25 kPa
- Max. allowed diff. Pressure sensor 2
- 120 kPa
- Damping (electronic)
- settable 1…12 s
- Unit. Range l/s
- 0…31000
- Unit. Range m3/h
- 0…65000 (factory setting)
Specifications
Protection class | IP54 |
---|---|
Ambient humidity (non-condensing) | 0…95 % RH |
Mounting | Wall |
Media | Air, non-combustible and non-aggressive gases |
Universal inputs type (UI) | PT1000*, Ni1000, 0...10 V, Digital input |
Universal outputs type (UO) | Configuration AO (AO / DO) 0…10, Configuration DO Mosfet outputs, 24 V AC or DC, 2 A continuous, Power output Max. 2A (total UO1 + UO2) |
Pressure, range sensor | 0…1250 Pa |
Cable gland | M16x1,5, M20x1,5 |
Terminal type | Screw Terminal |
Terminal wire size | 1.5 mm² |
Material, housing | Polycarbonate (PC) |
Material, base | Polycarbonate (PC) |
Software & documentation
Product sheet
Instructions
Manuals
Other documentation
Accessories
ANS-20
2 m plastic tube and two pressure outlets (straight)