Regin

Presigo (PDT…) - Differential pressure transmitters with analogue outputs

Single or dual port differential pressure transmitters with one or two analogue outputs. The transmitter can be configured for 0-10 V or 4-20 mA output signal. Selectable working range.

Articles

(5 st)
  • PDT12 - Regin
    PDT12
    Power Supply
    24VAC/DC (21...27 V AC 50Hz / 21...27 V DC), 2.7 VA
    Dimensions, external (WxHxD)
    120x40x112 mm
    Max Overvoltage on any terminal
    Max. ±18 V (referenced to GND) V
    Analogue output load impedance 0...10v
    Load impedance ≥ 10 kΩ, Output impedance ≤ 35Ω
    Analogue output load impedance 4...20mA
    Output is actively sourced into a resistive load impedance to signal ground. The load impedance must be between 40...500Ω
    Pressure, range sensor
    0…1250 Pa
    Accuracy, pressure sensor 1
    ≤ 1 % full scale %
    Max. allowed diff. Pressure sensor 1
    25 kPa
  • PDT25 - Regin
    PDT25
    Power Supply
    24VAC/DC (21...27 V AC 50Hz / 21...27 V DC), 2.7 VA
    Dimensions, external (WxHxD)
    120x40x112 mm
    Max Overvoltage on any terminal
    Max. ±18 V (referenced to GND) V
    Analogue output load impedance 0...10v
    Load impedance ≥ 10 kΩ, Output impedance ≤ 35Ω
    Analogue output load impedance 4...20mA
    Output is actively sourced into a resistive load impedance to signal ground. The load impedance must be between 40...500Ω
    Pressure, range sensor
    0…2500 Pa
    Accuracy, pressure sensor 1
    ≤ 1 % full scale %
    Max. allowed diff. Pressure sensor 1
    50 kPa
  • PDT75 - Regin
    PDT75
    Power Supply
    24VAC/DC (21...27 V AC 50Hz / 21...27 V DC), 2.7 VA
    Dimensions, external (WxHxD)
    120x40x112 mm
    Max Overvoltage on any terminal
    Max. ±18 V (referenced to GND) V
    Analogue output load impedance 0...10v
    Load impedance ≥ 10 kΩ, Output impedance ≤ 35Ω
    Analogue output load impedance 4...20mA
    Output is actively sourced into a resistive load impedance to signal ground. The load impedance must be between 40...500Ω
    Pressure, range sensor
    0…7500 Pa
    Accuracy, pressure sensor 1
    ≤ 1 % full scale %
    Max. allowed diff. Pressure sensor 1
    120 kPa
  • PDT12S25-2 - Regin
    PDT12S25-2
    Power Supply
    24VAC/DC (21...27 V AC 50Hz / 21...27 V DC), 2.7 VA
    Dimensions, external (WxHxD)
    120x40x112 mm
    Max Overvoltage on any terminal
    Max. ±18 V (referenced to GND) V
    Analogue output load impedance 0...10v
    Load impedance ≥ 10 kΩ, Output impedance ≤ 35Ω
    Analogue output load impedance 4...20mA
    Output is actively sourced into a resistive load impedance to signal ground. The load impedance must be between 40...500Ω
    Pressure, range sensor
    0…1250 Pa
    Pressure, range sensor 2
    0…2500 Pa
    Accuracy, pressure sensor 1
    ≤ 1 % full scale %
    Accuracy, pressure sensor 2
    ≤ 1 % full scale %
    Max. allowed diff. Pressure sensor 1
    25 kPa
    Max. allowed diff. Pressure sensor 2
    50 kPa
  • PDT12S75-2 - Regin
    PDT12S75-2
    Power Supply
    24VAC/DC (21...27 V AC 50Hz / 21...27 V DC), 2.7 VA
    Dimensions, external (WxHxD)
    120x40x112 mm
    Max Overvoltage on any terminal
    Max. ±18 V (referenced to GND) V
    Analogue output load impedance 0...10v
    Load impedance ≥ 10 kΩ, Output impedance ≤ 35Ω
    Analogue output load impedance 4...20mA
    Output is actively sourced into a resistive load impedance to signal ground. The load impedance must be between 40...500Ω
    Pressure, range sensor
    0…1250 Pa
    Pressure, range sensor 2
    0…7500 Pa
    Accuracy, pressure sensor 1
    ≤ 1 % full scale %
    Accuracy, pressure sensor 2
    ≤ 1 % full scale %
    Max. allowed diff. Pressure sensor 1
    25 kPa
    Max. allowed diff. Pressure sensor 2
    120 kPa

Specifications

Specifications for Presigo (PDT…) - Differential pressure transmitters with analogue outputs
Protection class IP54
Ambient humidity (non-condensing) 0…95 % RH
Mounting Wall
Media Air, non-combustible and non-aggressive gases
Analogue outputs type (AO) 0...10V or 4...20mA
Pressure, range sensor 0…1250 Pa
Cable gland M16x1,5
Terminal type Screw Terminal
Terminal wire size 1.5 mm²
Material, housing Polycarbonate (PC)
Material, base Polycarbonate (PC)

Accessories