Regin

Smoke detector for duct mounting, optical

Single-tube detector, including 600 mm Venturi tube.

Articles

(2 st)
  • SDD-OE65 - Regin
    SDD-OE65
    Optical detector with service alarm (max 20 sensors, to be connected to CABV control unit) including 600 mm Venturi tube.
    Power Supply
    9...33 V DC (via ABV control unit)
    Wind speed
    Up to 20 m/s
    Smoke alarm
    Red LED
    Service alarm
    Red LED on detector. Yellow LED on control unit.
    Current consumption, normal
    10 mA
    Current consumption during alarm
    50 mA
    Current consumption during service alarm
    20 mA
    End resistor
    An end resistor (2,2 kΩ) should be connected to the last detector to end the loop.
  • SDD-OE65-RAC - Regin
    SDD-OE65-RAC
    Optical detector with AC power supply and relay output only, with service alarm, including 600 mm Venturi tube.
    Power Supply
    24 V AC ±15 % for RAC(M) models.
    Wind speed
    Up to 20 m/s
    Smoke alarm
    Red LED
    Service alarm
    Red LED on detector. Yellow LED on control unit.
    Current consumption, normal
    10 mA
    Current consumption during alarm
    50 mA
    Current consumption during service alarm
    20 mA
    Relay
    Max 24 V AC / 2A or 24 V DC / 1A (Resistive load)
    End resistor
    An end resistor (2,2 kΩ) should be connected to the last detector to end the loop.

Specifications

Specifications for Smoke detector for duct mounting, optical
Protection class IP54
Ambient humidity (non-condensing) 5…95 % RH
Mounting Duct

Accessories