Regin

I/O module with 16 analogue inputs

I/O module for expansion of Regin’s programmable EXOclever, EXOflex, EXOcompact and EXOdos controllers.

Articles

(1 st)
  • IO-16AI - Regin
    IO-16AI
    Input module
    Power Supply
    24VAC (20...28 V AC 50Hz / ), 3.5 VA
    Dimensions, external (WxHxD)
    148x123x59 mm
    Number of modules
    8.5
    Supported protocols
    EXOline
    RS485 ports
    1
    AI
    16

Specifications

Specifications for I/O module with 16 analogue inputs
Protection class IP20
Mounting DIN-rail
Analogue inputs type (AI) PT1000, Ni1000 (only CAN-Bus), microsensors, 0…10 kΩ, 0...10 V, 0(4)...20 mA
Terminal wire size 1.5 mm²