Regin

GF - 2- and 3-way control valves, DN25-200, kvs 6.3-550, DIN-standard

Control valves for use in heating, cooling and ventilation systems. They are intended to be used together with Regin’s RVAN actuators. The valves have DIN-standard lengths.

Articles

(26 st)
  • GF325-10 - Regin
    GF325-10
    Actuator connection
    Standard for RVAN5.../RVAN10... actuators
    Rangeability
    50:1
    Stroke
    20 mm
    Nominal diameter
    DN25
    Kvs
    10 m³/h
    Max. diff. pressure
    1300 kPa
    Media temperature
    -5…120 °C
  • GF225-6.3 - Regin
    GF225-6.3
    Actuator connection
    Standard for RVAN5.../RVAN10... actuators
    Rangeability
    50:1
    Stroke
    20 mm
    Nominal diameter
    DN25
    Kvs
    6.3 m³/h
    Max. diff. pressure
    1300 kPa
    Media temperature
    -5…120 °C
  • GF225-10 - Regin
    GF225-10
    Actuator connection
    Standard for RVAN5.../RVAN10... actuators
    Rangeability
    50:1
    Stroke
    20 mm
    Nominal diameter
    DN25
    Kvs
    10 m³/h
    Max. diff. pressure
    1300 kPa
    Media temperature
    -5…120 °C
  • GF232-10 - Regin
    GF232-10
    Actuator connection
    Standard for RVAN5.../RVAN10... actuators
    Rangeability
    50:1
    Stroke
    20 mm
    Nominal diameter
    DN32
    Kvs
    10 m³/h
    Max. diff. pressure
    800 kPa
    Media temperature
    -5…120 °C
  • GF232-16 - Regin
    GF232-16
    Actuator connection
    Standard for RVAN5.../RVAN10... actuators
    Rangeability
    50:1
    Stroke
    20 mm
    Nominal diameter
    DN32
    Kvs
    16 m³/h
    Max. diff. pressure
    800 kPa
    Media temperature
    -5…120 °C
  • GF240-16 - Regin
    GF240-16
    Actuator connection
    Standard for RVAN5.../RVAN10... actuators
    Rangeability
    50:1
    Stroke
    20 mm
    Nominal diameter
    DN40
    Kvs
    16 m³/h
    Max. diff. pressure
    550 kPa
    Media temperature
    -5…120 °C
  • GF240-25 - Regin
    GF240-25
    Actuator connection
    Standard for RVAN5.../RVAN10... actuators
    Rangeability
    50:1
    Stroke
    20 mm
    Nominal diameter
    DN40
    Kvs
    25 m³/h
    Max. diff. pressure
    550 kPa
    Media temperature
    -5…120 °C
  • GF250-31.5 - Regin
    GF250-31.5
    Actuator connection
    Standard for RVAN18.../RVAN25... actuators
    Rangeability
    100:1
    Stroke
    20 mm
    Nominal diameter
    DN50
    Kvs
    31.5 m³/h
    Max. diff. pressure
    350 kPa
    Media temperature
    -5…120 °C
  • GF250-40 - Regin
    GF250-40
    Actuator connection
    Standard for RVAN18.../RVAN25... actuators
    Rangeability
    100:1
    Stroke
    20 mm
    Nominal diameter
    DN50
    Kvs
    40 m³/h
    Max. diff. pressure
    350 kPa
    Media temperature
    -5…120 °C
  • GF265-50 - Regin
    GF265-50
    Actuator connection
    Standard for RVAN18.../RVAN25... actuators
    Rangeability
    100:1
    Stroke
    20 mm
    Nominal diameter
    DN65
    Kvs
    50 m³/h
    Max. diff. pressure
    200 kPa
    Media temperature
    -5…120 °C
  • GF265-63 - Regin
    GF265-63
    Actuator connection
    Standard for RVAN18.../RVAN25... actuators
    Rangeability
    100:1
    Stroke
    20 mm
    Nominal diameter
    DN65
    Kvs
    63 m³/h
    Max. diff. pressure
    200 kPa
    Media temperature
    -5…120 °C
  • GF280-80 - Regin
    GF280-80
    Actuator connection
    Standard for RVAN18.../RVAN25... actuators
    Rangeability
    100:1
    Stroke
    40 mm
    Nominal diameter
    DN80
    Kvs
    80 m³/h
    Max. diff. pressure
    350 kPa
    Media temperature
    -5…120 °C
  • GF280-100 - Regin
    GF280-100
    Actuator connection
    Standard for RVAN18.../RVAN25... actuators
    Rangeability
    100:1
    Stroke
    40 mm
    Nominal diameter
    DN80
    Kvs
    100 m³/h
    Max. diff. pressure
    350 kPa
    Media temperature
    -5…120 °C
  • GF2100-125 - Regin
    GF2100-125
    Actuator connection
    Standard for RVAN18.../RVAN25... actuators
    Rangeability
    100:1
    Stroke
    40 mm
    Nominal diameter
    DN100
    Kvs
    125 m³/h
    Max. diff. pressure
    200 kPa
    Media temperature
    -5…120 °C
  • GF2125-215 - Regin
    GF2125-215
    Actuator connection
    Standard for RVAN18.../RVAN25... actuators
    Rangeability
    100:1
    Stroke
    40 mm
    Nominal diameter
    DN125
    Kvs
    215 m³/h
    Max. diff. pressure
    120 kPa
    Media temperature
    -5…120 °C
  • GF2150-310 - Regin
    GF2150-310
    Actuator connection
    Standard for RVAN18.../RVAN25... actuators
    Rangeability
    100:1
    Stroke
    40 mm
    Nominal diameter
    DN150
    Kvs
    310 m³/h
    Max. diff. pressure
    100 kPa
    Media temperature
    -5…120 °C
  • GF325-6.3 - Regin
    GF325-6.3
    Actuator connection
    Standard for RVAN5.../RVAN10... actuators
    Rangeability
    50:1
    Stroke
    20 mm
    Nominal diameter
    DN25
    Kvs
    6.3 m³/h
    Max. diff. pressure
    1300 kPa
    Media temperature
    -5…120 °C
  • GF332-16 - Regin
    GF332-16
    Actuator connection
    Standard for RVAN5.../RVAN10... actuators
    Rangeability
    50:1
    Stroke
    20 mm
    Nominal diameter
    DN32
    Kvs
    16 m³/h
    Max. diff. pressure
    800 kPa
    Media temperature
    -5…120 °C
  • GF340-16 - Regin
    GF340-16
    Actuator connection
    Standard for RVAN5.../RVAN10... actuators
    Rangeability
    50:1
    Stroke
    20 mm
    Nominal diameter
    DN40
    Kvs
    16 m³/h
    Max. diff. pressure
    550 kPa
    Media temperature
    -5…120 °C
  • GF340-25 - Regin
    GF340-25
    Actuator connection
    Standard for RVAN5.../RVAN10... actuators
    Rangeability
    50:1
    Stroke
    20 mm
    Nominal diameter
    DN40
    Kvs
    25 m³/h
    Max. diff. pressure
    550 kPa
    Media temperature
    -5…120 °C
  • GF350-31.5 - Regin
    GF350-31.5
    Actuator connection
    Standard for RVAN18.../RVAN25... actuators
    Rangeability
    100:1
    Stroke
    20 mm
    Nominal diameter
    DN50
    Kvs
    31.5 m³/h
    Max. diff. pressure
    350 kPa
    Media temperature
    -5…120 °C
  • GF350-40 - Regin
    GF350-40
    Actuator connection
    Standard for RVAN18.../RVAN25... actuators
    Rangeability
    100:1
    Stroke
    20 mm
    Nominal diameter
    DN50
    Kvs
    40 m³/h
    Max. diff. pressure
    350 kPa
    Media temperature
    -5…120 °C
  • GF365-50 - Regin
    GF365-50
    Actuator connection
    Standard for RVAN18.../RVAN25... actuators
    Rangeability
    100:1
    Stroke
    20 mm
    Nominal diameter
    DN65
    Kvs
    50 m³/h
    Max. diff. pressure
    200 kPa
    Media temperature
    -5…120 °C
  • GF365-63 - Regin
    GF365-63
    Actuator connection
    Standard for RVAN18.../RVAN25... actuators
    Rangeability
    100:1
    Stroke
    20 mm
    Nominal diameter
    DN65
    Kvs
    63 m³/h
    Max. diff. pressure
    200 kPa
    Media temperature
    -5…120 °C
  • GF3125-215 - Regin
    GF3125-215
    Actuator connection
    Standard for RVAN18.../RVAN25... actuators
    Rangeability
    100:1
    Stroke
    40 mm
    Nominal diameter
    DN125
    Kvs
    215 m³/h
    Max. diff. pressure
    120 kPa
    Media temperature
    -5…120 °C
  • GF3150-310 - Regin
    GF3150-310
    Actuator connection
    Standard for RVAN18.../RVAN25... actuators
    Rangeability
    100:1
    Stroke
    40 mm
    Nominal diameter
    DN150
    Kvs
    310 m³/h
    Max. diff. pressure
    100 kPa
    Media temperature
    -5…120 °C

Specifications

Specifications for GF - 2- and 3-way control valves, DN25-200, kvs 6.3-550, DIN-standard
Application Heating, Cooling, Ventilation
Pressure rating PN16
Connection types Flanged according to EN 1092-2
Flow characteristics Equal percentage
Leakage 0.0 % of Kvs (No leakage)
Media Hot water, Cold water, Glycol-mixed water (max. 50 % glycol)
Closing direction When stem is pulled outward
Max. diff. pressure 1300 kPa
Media temperature -5…120 °C
Body Grey cast iron EN-GJL-250, EN-JL1040
Seat Grey cast iron EN-GJL-250, EN-JL1040
Plug Brass CW614N
Stem Stainless steel 1.4305
Seat packing EPDM
O-rings EPDM
Stuffing box Brass CW614N
Bonnet Brass CW614N

Accessories