Regin
DTTHC Temperature, humidity and CO 2 transmitter for duct mounting
Temperature, humidity and CO2 transmitter
Navigate on this page
Specifications
Mounting | Duct |
---|---|
Power Supply | 24VAC/DC (20...28 V AC 50/60Hz / 15...35 V DC), 2.0 VA |
Dimensions, external (WxHxD) | 104x212x79 mm |
AO | 3 |
Max air velocity | 20 m/s |
Media temp limits | -40…60 °C |
Insertion length | 37…195 mm |
Max Overvoltage on any terminal | +10 V (refereras till GND) V |
Analogue output load impedance 0...10v | Min. 10 kΩ |
Measuring range, temp | -40…60 °C |
Output temperature | 0-10 V |
Measuring range, humidity | 0…100 % RH |
Output humidity | 0-10 V |
Sensor element protection, humidity | Membrane filter, not exchangeable |
Accuracy, humidity 1 | ± % RH @ 10...90 |
Accuracy, humidity 2 | ± % RH @ 0...10 & 90...100 |
Measuring range, gas in air | 0…2000 ppm |
Output signal, gas in air | 0-10 V |
Accuracy, gas in air | ±(50 ppm + 3 % of the measured value) @ 25 °C |
Response time | <100s |
Warm-up time | 4min |
Temperature dependance | 2.5 ppm/K at 0…50 °C |
Protection class | IP65 |
---|---|
Ambient humidity (non-condensing) | 0…90 % RH |
Storage temperature | -40…80 °C |
Storage humidity | 0...90 % RH |
Weight, incl. packaging | 0.25 kg |
Accuracy, temperature | 0,2 K |
Accuracy, temperature 1 | ±0.2 °K @ 0...60 °C |
Accuracy, temperature 2 | ±0.8 °K @ -40...0 & >60 °C |
Cable gland | M16x1,5 |
Terminal type | Screw Terminal |
Terminal wire size | 1.5 mm² |
Material, housing | Polykarbonat (PC) |
Material, cover | Polykarbonat (PC) |
Material, base | ABS |