Regin

Temperature and CO2 transmitter for duct mounting

0…10 V duct transmitter for temperature and carbon dioxide measurements in air.

Articles

(1 st)
  • DTTC - Regin
    DTTC
    Power Supply
    24VAC/DC (20...28 V AC 50/60Hz / 15...35 V DC), 2.0 VA
    Dimensions, external (WxHxD)
    104x212x79 mm
    AO
    2
    Max air velocity
    20 m/s
    Media temp limits
    -40…60 °C
    Insertion length
    37…195 mm
    Max Overvoltage on any terminal
    +10 V (refereras till GND) V
    Analogue output load impedance 0...10v
    Min. 10 kΩ
    Measuring range, temp
    -40…60 °C
    Output temperature
    0-10 V
    Measuring range, gas in air
    0…2000 ppm
    Output signal, gas in air
    0-10 V
    Accuracy, gas in air
    ±(50 ppm + 3 % of measured value) @ 25 °C
    Response time
    <100s
    Warm-up time
    4min
    Temperature dependance
    2.5 ppm/K at 0…50 °C

Specifications

Specifications for Temperature and CO2 transmitter for duct mounting
Protection class IP65
Ambient humidity (non-condensing) 0…90 % RH
Storage temperature -40…80 °C
Storage humidity 0...90 % RH
Weight, incl. packaging 0.25 kg
Accuracy, temperature 0,2 K
Accuracy, temperature 1 ±0.2 °K @ 0...60 °C
Accuracy, temperature 2 ±0.8 °K @ -40...0 & >60 °C
Cable gland M16x1,5
Terminal type Screw Terminal
Terminal wire size 1.5 mm²
Material, housing Polykarbonat (PC)
Material, cover Polykarbonat (PC)
Material, base ABS