(0 st)Specifications
Supply voltage | 24 V AC ±20 %, 50...60 Hz or 15...35 V DC, 3 VA |
---|---|
Working range | 0...2000 ppm |
Accuracy | ±(50 ppm + 2 % of the measured value) |
Relay output | Max. 1 A at 50 V AC, min. 1 mA at 5 V DC |
Mounting | Duct |
Protection class | IP65 |
Calibration | Automatic |