Specifications

Specifications for TG-KH3/PT100
Mounting Duct
Dimensions, external (WxHxD) 78x263x104 mm
Media temp limits -30…70 °C
Insertion length 60…200 mm
Time constant 16 s
Diameter, well 8 mm
Element type PT100
Measuring range, temp -30…70 °C
Sensor element, class DIN Class B: ±(0.3 + .005 |T|°C)
Nominal resistance 100 Ω (0°C)
Specifications for Duct sensor with housing
Protection class IP65
Mounting Duct
Weight, incl. packaging 0.19 kg
Cable gland M16x1,5
Terminal type Screw Terminal
Detachable terminal Yes
Terminal wire size 1.5 mm²
Material, housing Polycarbonate (PC)
Material, base Polycarbonate (PC)
Material sensor Stainless steel, EU1.4301 (SUS304)