Regin

SSCU50-15-HR-MPI Flanged ultrasonic energy meters

Flanged ultrasonic energy meters, intended for heating or cooling.We offer many different options, see the product sheet for more information.

Specifications

Specifications for SSCU50-15-HR-MPI
Power Supply Exchangeable 3 V lithium battery, estimated lifetime 10 years. 24 V or 230 V power pack available as accessory.
Nominal diameter DN50
Flow, Qp 15 m³/h
Type of measurement Heating
Communication interface M-Bus with 3 pulse inputs
Length of flow meter 270 mm
Media Water only
Specifications for Flanged ultrasonic energy meters
Protection class IP54
Ambient humidity (non-condensing) 5…95 % RH
Storage temperature 1…60 °C
Temperature range cooling 0...50 °C
Temperature range heating 0...150 °C
Temperature resolution 0.01 °C
Measurement cycle, temperature 2...60 s
Measurement cycle, flow 2 s
Display LCD, 8 digits + special characters
Display units MWh, kW, GJ, m 3 , m 3 /h (kWh, GJ, l , l/h, MW, MMBTU, Gcal), 3 decimal places. The unit for energy consumption can only be set while the energy consumption is ≤ 10 kWh.
Mechanical class Class M2 (MID: 31.03.2004 annex I)
EMC Class E2 (MID: 31.03.2004 annex I)
Cable length temperature sensor 3 m
Diameter temperature sensor 6 mm
Temperature sensor installation Indirect in a temperature sensor pocket per EN1434
Temperature sensor requirements, heat meter EU (MID) identification on the temperature sensors
Temperature sensor requirements, cooling meter National German approval as a temperature sensor for cooling meters. Requirements in other countries may be different
Flow meter mounting position Horizontal or vertical, the transducers (black housing) to the side of or under the measuring tube for cooling applications
Flow meter, point of installation Return flow (if forward flow installation is needed, the installation position can be changed with the main button)
Flow meter temperature range Heating 10…130 °C
Measuring principle Ultrasonic; time-of-flight
Accuracy according to MID Class 2

Accessories