Specifications for LON
Supply voltage |
24 V AC ±15 %, 50...60 Hz or 20...36 V DC |
Power consumption |
5 VA |
Display |
Backlit, LCD, 4 rows of 20 characters, international character set |
Dimensions (WxHxD) |
148 x 123 x 58 mm, 8.5 modulesmm |
Protection class |
IP20 |
Mounting |
DIN-rail or cabinet |
Analogue inputs (AI) |
0...10 V DC, 0...200 mV, PT1000, DIN Ni1000, LGNi1000, 12-bit A/D |
Digital inputs (DI) |
Floating switch, 24 V DC, configurable for pulse input |
Universal inputs (UI) |
AI or DI (see above) |
Analogue outputs (AO) |
0...10 V DC, 5 mA, 8-bit D/A, short-circuit proof |
Digital outputs (DO) |
Mosfet 24 V AC/DC, 2 A. Totally max. 8 A. |
24 V DC output |
0.1 A, short-circuit proof |
Communication |
EXOline, Modbus or dial-up connection Port 1, isolated, via a built-in RS485 connector. Modems are available as accessories for Port 1. There are models with TCP/IP or LON communication. |
Operating system |
EXOreal |
Battery backup |
Memory and real-time clock, at least 5 years |
LON |
FT3150, gives a second communication route |
Ethernet |
EXOline (Port 1) over TCP/IP instead of RS485 |