Regin

BV - 2- and 3-way ball valves, DN15-50, kvs 0.6-63

Ball valves designed for control of hot, cold or glycol-mixed water in heating and ventilation systems. These ball valves can be used as either characterized control ball valves when a flow plate is installed in port A (default mode), or as on/off ball valves when the flow plate is removed. When the flow plate is removed the Kvs between port A and AB is increased. The valves are intended for use with Regin's RVAB4/RVAB5 actuators.

Articles

(10 st)
  • BV215 - Regin
    BV215
    Connection
    G1/2"
    Actuator connection
    Standard for RVAB4 actuators
    Rangeability
    100:1
    Nominal diameter
    DN15
    Kvs, adjustable
    0.6/1.0/1.6/2.5/4.0 m³/h
    Max. diff. pressure
    2500 kPa
  • BV220 - Regin
    BV220
    Connection
    G3/4"
    Actuator connection
    Standard for RVAB4 actuators
    Rangeability
    100:1
    Nominal diameter
    DN20
    Kvs
    6.3 m³/h
    Max. diff. pressure
    2500 kPa
  • BV225 - Regin
    BV225
    Connection
    G1"
    Actuator connection
    Standard for RVAB4 actuators
    Rangeability
    100:1
    Nominal diameter
    DN25
    Kvs
    10 m³/h
    Max. diff. pressure
    2500 kPa
  • BV232 - Regin
    BV232
    Connection
    G1 1/4"
    Actuator connection
    Standard for RVAB5 actuators
    Rangeability
    100:1
    Nominal diameter
    DN32
    Kvs
    16 m³/h
    Max. diff. pressure
    1600 kPa
  • BV240 - Regin
    BV240
    Connection
    G1 1/2"
    Actuator connection
    Standard for RVAB5 actuators
    Rangeability
    100:1
    Nominal diameter
    DN40
    Kvs
    25 m³/h
    Max. diff. pressure
    1600 kPa
  • BV315 - Regin
    BV315
    Connection
    G1/2"
    Actuator connection
    Standard for RVAB4 actuators
    Rangeability
    100:1
    Nominal diameter
    DN15
    Kvs, adjustable
    0.6/1.0/1.6/2.5/4.0 m³/h
    Max. diff. pressure
    2500 kPa
  • BV320 - Regin
    BV320
    Connection
    G3/4"
    Actuator connection
    Standard for RVAB4 actuators
    Rangeability
    100:1
    Nominal diameter
    DN20
    Kvs
    6.3 m³/h
    Max. diff. pressure
    2500 kPa
  • BV325 - Regin
    BV325
    Connection
    G1"
    Actuator connection
    Standard for RVAB4 actuators
    Rangeability
    100:1
    Nominal diameter
    DN25
    Kvs
    10 m³/h
    Max. diff. pressure
    2500 kPa
  • BV332 - Regin
    BV332
    Connection
    G1 1/4"
    Actuator connection
    Standard for RVAB5 actuators
    Rangeability
    100:1
    Nominal diameter
    DN32
    Kvs
    16 m³/h
    Max. diff. pressure
    1600 kPa
  • BV340 - Regin
    BV340
    Connection
    G1 1/2"
    Actuator connection
    Standard for RVAB5 actuators
    Rangeability
    100:1
    Nominal diameter
    DN40
    Kvs
    25 m³/h
    Max. diff. pressure
    1600 kPa

Specifications

Specifications for BV - 2- and 3-way ball valves, DN15-50, kvs 0.6-63
Application Cooling, Ventilation, Heating, Fan coil
Pressure rating PN40
Connection types BSP internally threaded according to ISO 228/1
Flow characteristics Equal percentage
Leakage 0.0 % of Kvs (No leakage)
Media Hot water, Cold water, Glycol-mixed water (max. 50 % glycol)
Angle of rotation 90 °
Media temperature -5…140 °C
Body Brass CW617N
Seat PTFE
Stem Stainless steel 1.4305
Ball Chromed brass CW614N
Flow plate POM
Circlips Stainless steel 1.4310
O-rings EPDM
Gasket EPDM

Accessories