Navigate on this page
Articles
(2 st)-
CTRCCO2 + °C
- Power Supply
- 24VAC/DC (22...26 V AC 50Hz / 15...35 V DC), 2.5 VA
- Dimensions, external (WxHxD)
- 100x85x30 mm
- Supported protocols
- Modbus
- Measuring range, temp
- 0…50 °C
- Output temperature
- Modbus
- Measuring range, gas in air
- 0…2000 ppm
- Output signal, gas in air
- Modbus
- Accuracy, gas in air
- < ± (50 ppm + 2 % of the measured value)
- Long term stability
- Typically 20 ppm / year
- Warm-up time
- < 5 min
- Temperature dependance
- Typically 5 ppm / K
-
CTRC-DCO2 + °C
- Power Supply
- 24VAC/DC (22...26 V AC 50Hz / 15...35 V DC), 2.5 VA
- Dimensions, external (WxHxD)
- 100x85x30 mm
- Display
- Yes
- Supported protocols
- Modbus
- Measuring range, temp
- 0…50 °C
- Output temperature
- Modbus
- Measuring range, gas in air
- 0…2000 ppm
- Output signal, gas in air
- Modbus
- Accuracy, gas in air
- < ± (50 ppm + 2 % of the measured value)
- Long term stability
- Typically 20 ppm / year
- Warm-up time
- < 5 min
- Temperature dependance
- Typically 5 ppm / K
Specifications
Protection class | IP30 |
---|---|
Ambient humidity (non-condensing) | 10…90 % RH |
Storage temperature | -25…60 °C |
Mounting | Room |
Accuracy, temperature 1 | ±0.2 °K @ 0...50 °C |
Terminal type | Screw Terminal |
Terminal wire size | 1.5 mm² |
Material, housing | Polycarbonate (PC) |
Colour, housing | Signal white RAL 9003 |